Back to the backflow review queue

Backflow assembly test: Golden Diner

Approved

Filed Apr 10, 2024 by Emerson Brandt, Clearwater Backflow Testing. Filed from a phone.

Report

Date of service
Apr 10, 2024
Assembly type
RP
Serial number
B837086
Size
1 1/2
Test gauge serial
G-2411
Gauge calibration date
Jan 21, 2024
Check valve 1
8.5 psid
Check valve 1 closed tight
Yes
Check valve 2
1.8 psid
Relief valve opened at
2.9 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Emerson Brandt, current on the service date
  • All required fields present
  • Address matches parcel 007-30-01234
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

4954 Orchard Dr
Owner: Harlow Holdings LLC
Parcel 007-30-01234