Backflow assembly test: Golden Diner

Approved

Filed May 24, 2026 by Jamie Wexler, Northstar Plumbing & Backflow. Read in from a paper form and confirmed by staff.

Report

Date of service
May 24, 2026
Assembly type
RP
Serial number
B837086
Size
1 1/2
Test gauge serial
G-2149
Gauge calibration date
Dec 22, 2025
Check valve 1
8.9 psid
Check valve 1 closed tight
Yes
Check valve 2
2.5 psid
Relief valve opened at
4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Jamie Wexler, current on the service date
  • All required fields present
  • Address matches parcel 007-30-01234
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

4954 Orchard Dr
Owner: Harlow Holdings LLC
Parcel 007-30-01234