Back to the backflow review queue

Backflow assembly test: 5440 Stone Gate Ct

Approved

Filed May 18, 2024 by Sam Fairley, Northstar Plumbing & Backflow. Filed from a phone.

Report

Date of service
May 18, 2024
Assembly type
DC
Serial number
A367710
Size
3/4
Test gauge serial
G-4534
Gauge calibration date
Dec 5, 2023
Check valve 1
6.8 psid
Check valve 1 closed tight
Yes
Check valve 2
2.4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Sam Fairley, current on the service date
  • All required fields present
  • Address matches parcel 007-36-01086
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

5440 Stone Gate Ct
Owner: Drew Ashby
Parcel 007-36-01086