Back to the backflow review queue

Backflow assembly test: Maple Leaf Grill

Filed Nov 25, 2026 by Jamie Wexler, Northstar Plumbing & Backflow. Filed from a phone.

Report

Date of service
Nov 25, 2026
Assembly type
RP
Serial number
W347786
Size
1 1/2
Test gauge serial
G-3533
Gauge calibration date
Jun 30, 2026
Check valve 1
7.9 psid
Check valve 1 closed tight
Yes
Check valve 2
2.8 psid
Relief valve opened at
3.5 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Jamie Wexler, current on the service date
  • All required fields present
  • Address matches parcel 007-14-01328
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Property

7687 Orchard Trl
Owner: Harlow Holdings LLC
Parcel 007-14-01328