Back to the backflow review queue

Backflow assembly test: 5603 Quarry Trl

Approved

Filed Aug 18, 2025 by Reese Ellery, Heritage Plumbing & Backflow. Filed from a phone.

Report

Date of service
Aug 18, 2025
Assembly type
DC
Serial number
B173437
Size
3/4
Test gauge serial
G-8300
Gauge calibration date
Sep 26, 2024
Check valve 1
6.2 psid
Check valve 1 closed tight
Yes
Check valve 2
2.8 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Reese Ellery, current on the service date
  • All required fields present
  • Address matches parcel 045-28-01152
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

5603 Quarry Trl
Owner: Sam Harlow
Parcel 045-28-01152