Back to the backflow review queue

Backflow assembly test: 4554 Hickory Way

Approved

Filed Mar 2, 2025 by Cameron Whitcomb, Patriot Plumbing & Backflow. Read in from a paper form and confirmed by staff.

Report

Date of service
Mar 2, 2025
Assembly type
PVB
Serial number
K708013
Size
1
Test gauge serial
G-3177
Gauge calibration date
Oct 9, 2024
Check valve 1
7 psid
Check valve 1 closed tight
Yes
Check valve 2
1.3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Cameron Whitcomb, current on the service date
  • All required fields present
  • Address matches parcel 045-74-01219
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

4554 Hickory Way
Owner: Drew Danner
Parcel 045-74-01219