Back to the backflow review queue

Backflow assembly test: 5261 Meadow Lark Ln

Approved

Filed Aug 13, 2025 by Drew Vance, Clearwater Plumbing & Backflow. Filed from a phone.

Report

Date of service
Aug 13, 2025
Assembly type
RP
Serial number
K845218
Size
3/4
Test gauge serial
G-5436
Gauge calibration date
Feb 16, 2025
Check valve 1
8.7 psid
Check valve 1 closed tight
Yes
Check valve 2
1.4 psid
Relief valve opened at
4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Drew Vance, current on the service date
  • All required fields present
  • Address matches parcel 045-90-01301
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

5261 Meadow Lark Ln
Owner: Jordan Marsh
Parcel 045-90-01301