Backflow assembly test: 4090 Fox Run Trl

Approved

Filed Oct 1, 2024 by Drew Vance, Clearwater Plumbing & Backflow. Filed from a phone.

Report

Date of service
Oct 1, 2024
Assembly type
RP
Serial number
Z153466
Size
3/4
Test gauge serial
G-5716
Gauge calibration date
Dec 17, 2023
Check valve 1
8.9 psid
Check valve 1 closed tight
Yes
Check valve 2
1.7 psid
Relief valve opened at
3.4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Drew Vance, current on the service date
  • All required fields present
  • Address matches parcel 045-83-01114
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

4090 Fox Run Trl
Owner: Riley Nguyen
Parcel 045-83-01114