Back to the backflow review queue

Backflow assembly test: Hilltop Apartments

Approved

Filed Jun 2, 2024 by Drew Vance, Clearwater Plumbing & Backflow. Read in from a paper form and confirmed by staff.

Report

Date of service
Jun 2, 2024
Assembly type
DC
Serial number
K101643
Size
4
Test gauge serial
G-2628
Gauge calibration date
Jul 26, 2023
Check valve 1
8.5 psid
Check valve 1 closed tight
Yes
Check valve 2
3.7 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Drew Vance, current on the service date
  • All required fields present
  • Address matches parcel 045-13-01098
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

7407 Old Church Dr
Owner: Marsh Holdings LLC
Parcel 045-13-01098