Backflow assembly test: 8207 Pine Knoll Dr

Approved

Filed May 7, 2026 by Reese Ellery, Heritage Plumbing & Backflow. Filed from a phone.

Report

Date of service
May 7, 2026
Assembly type
PVB
Serial number
Z774694
Size
3/4
Test gauge serial
G-2839
Gauge calibration date
Mar 29, 2026
Check valve 1
4 psid
Check valve 1 closed tight
Yes
Check valve 2
2.9 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Reese Ellery, current on the service date
  • All required fields present
  • Address matches parcel 045-16-01006
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

8207 Pine Knoll Dr
Owner: Jordan Danner
Parcel 045-16-01006