Back to the backflow review queue

Backflow assembly test: Riverside Apartments

Approved

Filed Jul 24, 2024 by Cameron Whitcomb, Patriot Plumbing & Backflow. Filed from a phone.

Report

Date of service
Jul 24, 2024
Assembly type
RP
Serial number
K445404
Size
1
Test gauge serial
G-6831
Gauge calibration date
Mar 21, 2024
Check valve 1
6 psid
Check valve 1 closed tight
Yes
Check valve 2
3.1 psid
Relief valve opened at
2.6 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Cameron Whitcomb, current on the service date
  • All required fields present
  • Address matches parcel 045-89-01197
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

1080 Pine Knoll Ln
Owner: Vance Holdings LLC
Parcel 045-89-01197