Back to the backflow review queue

Backflow assembly test: 7919 Stone Gate Trl

Approved

Filed Oct 30, 2026 by Cameron Whitcomb, Patriot Plumbing & Backflow. Filed from a phone.

Report

Date of service
Oct 30, 2026
Assembly type
RP
Serial number
B479997
Size
3/4
Test gauge serial
G-6439
Gauge calibration date
Aug 10, 2025
Check valve 1
0.1 psid
Check valve 1 closed tight
No
Check valve 2
3.4 psid
Relief valve opened at
3.1 psid
Result
Fail
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Cameron Whitcomb, current on the service date
  • All required fields present
  • Address matches parcel 045-61-01013
  • Test gauge calibration is more than a year old.
  • Result: needs follow-up. The property stays on the overdue list until a passing report arrives.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

7919 Stone Gate Trl
Owner: Rowan Wexler
Parcel 045-61-01013