Backflow assembly test: 6248 Spring Branch Rd

Approved

Filed Sep 22, 2024 by Reese Ellery, Heritage Plumbing & Backflow. Filed from a phone.

Report

Date of service
Sep 22, 2024
Assembly type
PVB
Serial number
Z926109
Size
3/4
Test gauge serial
G-9204
Gauge calibration date
Jan 17, 2024
Check valve 1
7.9 psid
Check valve 1 closed tight
Yes
Check valve 2
1.5 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Reese Ellery, current on the service date
  • All required fields present
  • Address matches parcel 045-19-01161
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.