Backflow assembly test: 700 Spring Branch Trl
ApprovedFiled Nov 8, 2024 by Parker Ashby, Northstar Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Nov 8, 2024
- Assembly type
- DC
- Serial number
- K788041
- Size
- 3/4
- Test gauge serial
- G-2444
- Gauge calibration date
- Oct 4, 2024
- Check valve 1
- 8.8 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.5 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Parker Ashby, current on the service date
- All required fields present
- Address matches parcel 131-20-01164
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
700 Spring Branch Trl
Owner: Cameron Ramirez
Parcel 131-20-01164