Backflow assembly test: Hilltop Elementary School
ApprovedFiled May 18, 2026 by Emerson Benton, Summit Backflow Testing. Read in from a paper form and confirmed by staff.
Report
- Date of service
- May 18, 2026
- Assembly type
- RP
- Serial number
- A800850
- Size
- 1 1/2
- Test gauge serial
- G-1840
- Gauge calibration date
- Sep 17, 2025
- Check valve 1
- 5.5 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.6 psid
- Relief valve opened at
- 3.5 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Emerson Benton, current on the service date
- All required fields present
- Address matches parcel 131-25-01139
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
4992 Stone Gate Rd
Owner: Hollins Holdings LLC
Parcel 131-25-01139