Back to the backflow review queue

Backflow assembly test: Maple Leaf Brewing Co

Approved

Filed Sep 25, 2023 by Hayden Okafor, Northstar Backflow Testing. Read in from a paper form and confirmed by staff.

Report

Date of service
Sep 25, 2023
Assembly type
RP
Serial number
W729058
Size
2
Test gauge serial
G-4113
Gauge calibration date
Mar 4, 2023
Check valve 1
5.4 psid
Check valve 1 closed tight
Yes
Check valve 2
2.3 psid
Relief valve opened at
2.5 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Hayden Okafor, current on the service date
  • All required fields present
  • Address matches parcel 131-36-01083
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

3133 Turkey Hill Rd
Owner: Brandt Holdings LLC
Parcel 131-36-01083