Back to the backflow review queue

Backflow assembly test: Blue Heron Medical Offices

Approved

Filed Oct 27, 2023 by Hayden Okafor, Northstar Backflow Testing. Read in from a paper form and confirmed by staff.

Report

Date of service
Oct 27, 2023
Assembly type
DC
Serial number
B651141
Size
4
Test gauge serial
G-7856
Gauge calibration date
Aug 24, 2023
Check valve 1
4.2 psid
Check valve 1 closed tight
Yes
Check valve 2
2.5 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Hayden Okafor, current on the service date
  • All required fields present
  • Address matches parcel 131-34-01185
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

8600 Sycamore Trl
Owner: Ellery Holdings LLC
Parcel 131-34-01185