Back to the backflow review queue

Backflow assembly test: 4280 Hickory Way

Approved

Filed Apr 25, 2026 by Hayden Pruitt, Summit Backflow Testing. Read in from a paper form and confirmed by staff.

Report

Date of service
Apr 25, 2026
Assembly type
RP
Serial number
B353690
Size
1
Test gauge serial
G-4896
Gauge calibration date
Dec 16, 2025
Check valve 1
7.2 psid
Check valve 1 closed tight
Yes
Check valve 2
1.4 psid
Relief valve opened at
3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Hayden Pruitt, current on the service date
  • All required fields present
  • Address matches parcel 131-34-01087
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

4280 Hickory Way
Owner: Parker Nguyen
Parcel 131-34-01087