Backflow assembly test: 7411 Turkey Hill Ct

Approved

Filed May 26, 2026 by Emerson Benton, Summit Backflow Testing. Filed from a phone.

Report

Date of service
May 26, 2026
Assembly type
RP
Serial number
Z692454
Size
1
Test gauge serial
G-4708
Gauge calibration date
Feb 16, 2026
Check valve 1
4.5 psid
Check valve 1 closed tight
Yes
Check valve 2
2.5 psid
Relief valve opened at
2.3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Emerson Benton, current on the service date
  • All required fields present
  • Address matches parcel 131-38-01158
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.