Back to the backflow review queue

Backflow assembly test: 8534 Turkey Hill Ct

Approved

Filed Oct 2, 2026 by Logan Okafor, Northstar Plumbing & Backflow. Filed from a phone.

Report

Date of service
Oct 2, 2026
Assembly type
DC
Serial number
B507084
Size
1
Test gauge serial
G-5285
Gauge calibration date
Apr 28, 2026
Check valve 1
4.2 psid
Check valve 1 closed tight
Yes
Check valve 2
1.9 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Logan Okafor, current on the service date
  • All required fields present
  • Address matches parcel 131-58-01295
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

8534 Turkey Hill Ct
Owner: Morgan Pruitt
Parcel 131-58-01295