Back to the backflow review queue
Backflow assembly test: 1831 Hickory Rd
ApprovedFiled Oct 20, 2024 by Hayden Pruitt, Summit Backflow Testing. Filed from a phone.
Report
- Date of service
- Oct 20, 2024
- Assembly type
- RP
- Serial number
- B250988
- Size
- 3/4
- Test gauge serial
- G-6207
- Gauge calibration date
- May 8, 2024
- Check valve 1
- 8.4 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 4 psid
- Relief valve opened at
- 3.3 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Hayden Pruitt, current on the service date
- All required fields present
- Address matches parcel 131-60-01012
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
1831 Hickory Rd
Owner: Cameron Pruitt
Parcel 131-60-01012