Back to the backflow review queue

Backflow assembly test: 6100 Mill Creek Way

Approved

Filed Jun 17, 2026 by Emerson Benton, Summit Backflow Testing. Filed from a phone.

Report

Date of service
Jun 17, 2026
Assembly type
DC
Serial number
B520471
Size
3/4
Test gauge serial
G-4024
Gauge calibration date
Feb 14, 2026
Check valve 1
7.8 psid
Check valve 1 closed tight
Yes
Check valve 2
3.8 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Emerson Benton, current on the service date
  • All required fields present
  • Address matches parcel 131-24-01338
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

6100 Mill Creek Way
Owner: Alex Marsh
Parcel 131-24-01338