Backflow assembly test: 1251 Pine Knoll Rd
ApprovedFiled Apr 12, 2026 by Casey Danner, Lakeside Plumbing & Backflow. Read in from a paper form and confirmed by staff.
Report
- Date of service
- Apr 12, 2026
- Assembly type
- RP
- Serial number
- K793579
- Size
- 1
- Test gauge serial
- G-7140
- Gauge calibration date
- Jan 26, 2026
- Check valve 1
- 4.1 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.8 psid
- Relief valve opened at
- 3.2 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Casey Danner, current on the service date
- All required fields present
- Address matches parcel 143-67-01000
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.