Backflow assembly test: 1251 Pine Knoll Rd

Approved

Filed Apr 12, 2026 by Casey Danner, Lakeside Plumbing & Backflow. Read in from a paper form and confirmed by staff.

Report

Date of service
Apr 12, 2026
Assembly type
RP
Serial number
K793579
Size
1
Test gauge serial
G-7140
Gauge calibration date
Jan 26, 2026
Check valve 1
4.1 psid
Check valve 1 closed tight
Yes
Check valve 2
3.8 psid
Relief valve opened at
3.2 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Casey Danner, current on the service date
  • All required fields present
  • Address matches parcel 143-67-01000
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

1251 Pine Knoll Rd
Owner: Jamie Stroud
Parcel 143-67-01000