Back to the backflow review queue

Backflow assembly test: Main Street Bakery

Approved

Filed Aug 3, 2025 by Jamie Ashby, Summit Backflow Testing. Read in from a paper form and confirmed by staff.

Report

Date of service
Aug 3, 2025
Assembly type
RP
Serial number
A678381
Size
1
Test gauge serial
G-3585
Gauge calibration date
Nov 10, 2024
Check valve 1
3.5 psid
Check valve 1 closed tight
Yes
Check valve 2
1.1 psid
Relief valve opened at
3.2 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Jamie Ashby, current on the service date
  • All required fields present
  • Address matches parcel 143-97-01319
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

809 Meadow Lark Ln
Owner: Vance Holdings LLC
Parcel 143-97-01319