Backflow assembly test: Golden Grill

Approved

Filed Oct 15, 2025 by Blake Wexler, Lakeside Plumbing & Backflow. Read in from a paper form and confirmed by staff.

Report

Date of service
Oct 15, 2025
Assembly type
DC
Serial number
K109991
Size
4
Test gauge serial
G-4712
Gauge calibration date
Mar 9, 2025
Check valve 1
4.5 psid
Check valve 1 closed tight
Yes
Check valve 2
2.6 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Blake Wexler, current on the service date
  • All required fields present
  • Address matches parcel 143-80-01236
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

2689 Sycamore Dr
Owner: Ashby Holdings LLC
Parcel 143-80-01236