Backflow assembly test: Two Rivers Animal Hospital

Approved

Filed Nov 18, 2025 by Reese Fairley, Clearwater Backflow Testing. Filed from a phone.

Report

Date of service
Nov 18, 2025
Assembly type
RP
Serial number
Z311049
Size
4
Test gauge serial
G-2688
Gauge calibration date
Apr 16, 2025
Check valve 1
8.5 psid
Check valve 1 closed tight
Yes
Check valve 2
1.3 psid
Relief valve opened at
4.1 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Reese Fairley, current on the service date
  • All required fields present
  • Address matches parcel 143-47-01059
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.