Backflow assembly test: 8832 Stone Gate Rd

Approved

Filed Oct 15, 2026 by Reese Fairley, Clearwater Backflow Testing. Filed from a phone.

Report

Date of service
Oct 15, 2026
Assembly type
RP
Serial number
W693071
Size
3/4
Test gauge serial
G-4063
Gauge calibration date
Dec 13, 2025
Check valve 1
0.5 psid
Check valve 1 closed tight
No
Check valve 2
2.1 psid
Relief valve opened at
2.7 psid
Result
Fail
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Reese Fairley, current on the service date
  • All required fields present
  • Address matches parcel 143-33-01318
  • Readings in range, no flags
  • Result: needs follow-up. The property stays on the overdue list until a passing report arrives.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

8832 Stone Gate Rd
Owner: Sam Fairley
Parcel 143-33-01318