Backflow assembly test: 5792 Cedar Hollow Way

Approved

Filed Jul 22, 2024 by Reese Fairley, Clearwater Backflow Testing. Filed from a phone.

Report

Date of service
Jul 22, 2024
Assembly type
RP
Serial number
W956868
Size
1
Test gauge serial
G-3042
Gauge calibration date
Jul 8, 2023
Check valve 1
8.1 psid
Check valve 1 closed tight
Yes
Check valve 2
1.8 psid
Relief valve opened at
1.2 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Reese Fairley, current on the service date
  • All required fields present
  • Address matches parcel 143-74-01111
  • RP relief valve must open at 2.0 psid or more.
  • Test gauge calibration is more than a year old.
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.