Backflow assembly test: 6520 Stone Gate Way
ApprovedFiled Dec 30, 2025 by Taylor Pruitt, Summit Backflow Testing. Filed from a phone.
Report
- Date of service
- Dec 30, 2025
- Assembly type
- PVB
- Serial number
- Z326520
- Size
- 1
- Test gauge serial
- G-9981
- Gauge calibration date
- Dec 3, 2024
- Check valve 1
- 0.3 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 3.7 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Taylor Pruitt, current on the service date
- All required fields present
- Address matches parcel 143-66-01039
- Test gauge calibration is more than a year old.
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
6520 Stone Gate Way
Owner: Emerson Vance
Parcel 143-66-01039