Backflow assembly test: 5993 Turkey Hill Ln

Approved

Filed Dec 6, 2024 by Jamie Ashby, Summit Backflow Testing. Filed from a phone.

Report

Date of service
Dec 6, 2024
Assembly type
PVB
Serial number
W137733
Size
3/4
Test gauge serial
G-8092
Gauge calibration date
Jun 30, 2024
Check valve 1
3.5 psid
Check valve 1 closed tight
Yes
Check valve 2
1.2 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Jamie Ashby, current on the service date
  • All required fields present
  • Address matches parcel 143-74-01320
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

5993 Turkey Hill Ln
Owner: Taylor Brandt
Parcel 143-74-01320