Backflow assembly test: 5615 Cedar Hollow Dr

Approved

Filed Jun 27, 2024 by Casey Danner, Lakeside Plumbing & Backflow. Filed from a phone.

Report

Date of service
Jun 27, 2024
Assembly type
RP
Serial number
A478373
Size
3/4
Test gauge serial
G-2496
Gauge calibration date
Jan 24, 2024
Check valve 1
3.1 psid
Check valve 1 closed tight
Yes
Check valve 2
1.8 psid
Relief valve opened at
2.2 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Casey Danner, current on the service date
  • All required fields present
  • Address matches parcel 143-33-01263
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

5615 Cedar Hollow Dr
Owner: Morgan Ashby
Parcel 143-33-01263