Backflow assembly test: 4858 Ridgeview Ln

Approved

Filed Dec 5, 2025 by Reese Fairley, Clearwater Backflow Testing. Filed from a phone.

Report

Date of service
Dec 5, 2025
Assembly type
PVB
Serial number
K796203
Size
3/4
Test gauge serial
G-9118
Gauge calibration date
Nov 2, 2025
Check valve 1
3.7 psid
Check valve 1 closed tight
Yes
Check valve 2
3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Reese Fairley, current on the service date
  • All required fields present
  • Address matches parcel 143-55-01135
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

4858 Ridgeview Ln
Owner: Logan Hollins
Parcel 143-55-01135