Backflow assembly test: 1436 Fox Run Rd
ApprovedFiled Sep 25, 2025 by Casey Danner, Lakeside Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Sep 25, 2025
- Assembly type
- DC
- Serial number
- B974951
- Size
- 1
- Test gauge serial
- G-4310
- Gauge calibration date
- Feb 8, 2025
- Check valve 1
- 5 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.1 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Casey Danner, current on the service date
- All required fields present
- Address matches parcel 143-52-01315
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.