Backflow assembly test: 577 Old Church Way
ApprovedFiled Aug 4, 2025 by Taylor Pruitt, Summit Backflow Testing. Filed from a phone.
Report
- Date of service
- Aug 4, 2025
- Assembly type
- DC
- Serial number
- B692095
- Size
- 1
- Test gauge serial
- G-8942
- Gauge calibration date
- Apr 15, 2025
- Check valve 1
- 5.3 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.3 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Taylor Pruitt, current on the service date
- All required fields present
- Address matches parcel 143-32-01049
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.