Back to the backflow review queue

Backflow assembly test: 2426 Old Church Way

Approved

Filed Aug 31, 2026 by Taylor Pruitt, Summit Backflow Testing. Filed from a phone.

Report

Date of service
Aug 31, 2026
Assembly type
RP
Serial number
K164587
Size
1
Test gauge serial
G-6435
Gauge calibration date
Jan 5, 2026
Check valve 1
8.7 psid
Check valve 1 closed tight
Yes
Check valve 2
3.8 psid
Relief valve opened at
2.4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Taylor Pruitt, current on the service date
  • All required fields present
  • Address matches parcel 143-62-01249
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

2426 Old Church Way
Owner: Reese Harlow
Parcel 143-62-01249