Backflow assembly test: 8063 Stone Gate Rd

Approved

Filed May 22, 2026 by Taylor Pruitt, Summit Backflow Testing. Filed from a phone.

Report

Date of service
May 22, 2026
Assembly type
RP
Serial number
Z870736
Size
3/4
Test gauge serial
G-9840
Gauge calibration date
Mar 21, 2026
Check valve 1
8.8 psid
Check valve 1 closed tight
Yes
Check valve 2
1.1 psid
Relief valve opened at
3.1 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Taylor Pruitt, current on the service date
  • All required fields present
  • Address matches parcel 143-66-01230
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.