Back to the backflow review queue
Backflow assembly test: 3974 Orchard Trl
ApprovedFiled Mar 25, 2026 by Alex Benton, Heritage Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Mar 25, 2026
- Assembly type
- RP
- Serial number
- B882799
- Size
- 1
- Test gauge serial
- G-9496
- Gauge calibration date
- Oct 15, 2025
- Check valve 1
- 5.2 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.7 psid
- Relief valve opened at
- 3.6 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Alex Benton, current on the service date
- All required fields present
- Address matches parcel 001-94-01114
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.
Property
3974 Orchard Trl
Owner: Avery Vance
Parcel 001-94-01114