Backflow assembly test: Blue Heron Diner

Approved

Filed Oct 9, 2026 by Alex Benton, Heritage Plumbing & Backflow. Filed from a phone.

Report

Date of service
Oct 9, 2026
Assembly type
RP
Serial number
A364921
Size
1
Test gauge serial
G-7548
Gauge calibration date
Mar 22, 2026
Check valve 1
0.5 psid
Check valve 1 closed tight
No
Check valve 2
3.1 psid
Relief valve opened at
2.2 psid
Result
Fail
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Alex Benton, current on the service date
  • All required fields present
  • Address matches parcel 001-25-01197
  • Readings in range, no flags
  • Result: needs follow-up. The property stays on the overdue list until a passing report arrives.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

4009 Old Church Dr
Owner: Danner Holdings LLC
Parcel 001-25-01197