Backflow assembly test: Crossroads Bakery

Approved

Filed Nov 5, 2025 by Rowan Okafor, Ridge Backflow Testing. Read in from a paper form and confirmed by staff.

Report

Date of service
Nov 5, 2025
Assembly type
RP
Serial number
K639454
Size
4
Test gauge serial
G-3476
Gauge calibration date
Apr 22, 2025
Check valve 1
8.7 psid
Check valve 1 closed tight
Yes
Check valve 2
1.1 psid
Relief valve opened at
4.2 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Rowan Okafor, current on the service date
  • All required fields present
  • Address matches parcel 001-20-01211
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

2331 Turkey Hill Trl
Owner: Wexler Holdings LLC
Parcel 001-20-01211