Back to the backflow review queue

Backflow assembly test: Hilltop Apartments

Approved

Filed Jul 29, 2026 by Alex Benton, Heritage Plumbing & Backflow. Read in from a paper form and confirmed by staff.

Report

Date of service
Jul 29, 2026
Assembly type
RP
Serial number
B266862
Size
1 1/2
Test gauge serial
G-2461
Gauge calibration date
Mar 11, 2026
Check valve 1
8.2 psid
Check valve 1 closed tight
Yes
Check valve 2
1.4 psid
Relief valve opened at
3.1 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Alex Benton, current on the service date
  • All required fields present
  • Address matches parcel 001-62-01285
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

7578 Quarry Dr
Owner: Nguyen Holdings LLC
Parcel 001-62-01285