Backflow assembly test: 7866 Pine Knoll Ct

Approved

Filed Jul 29, 2025 by Alex Benton, Heritage Plumbing & Backflow. Filed from a phone.

Report

Date of service
Jul 29, 2025
Assembly type
RP
Serial number
K675991
Size
3/4
Test gauge serial
G-2001
Gauge calibration date
May 4, 2025
Check valve 1
4.4 psid
Check valve 1 closed tight
Yes
Check valve 2
3.2 psid
Relief valve opened at
3.1 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Alex Benton, current on the service date
  • All required fields present
  • Address matches parcel 001-16-01049
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

7866 Pine Knoll Ct
Owner: Blake Hollins
Parcel 001-16-01049