Back to the backflow review queue

Backflow assembly test: Golden Self Storage

Approved

Filed Apr 11, 2026 by Quinn Nguyen, Keystone Backflow Testing. Read in from a paper form and confirmed by staff.

Report

Date of service
Apr 11, 2026
Assembly type
RP
Serial number
A164810
Size
1
Test gauge serial
G-1134
Gauge calibration date
Dec 16, 2025
Check valve 1
6.7 psid
Check valve 1 closed tight
Yes
Check valve 2
2.5 psid
Relief valve opened at
3.6 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Quinn Nguyen, current on the service date
  • All required fields present
  • Address matches parcel 001-75-01220
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

6149 Stone Gate Rd
Owner: Benton Holdings LLC
Parcel 001-75-01220