Backflow assembly test: Hilltop Self Storage

Approved

Filed Jul 17, 2024 by Alex Benton, Heritage Plumbing & Backflow. Filed from a phone.

Report

Date of service
Jul 17, 2024
Assembly type
RP
Serial number
W135396
Size
1
Test gauge serial
G-4765
Gauge calibration date
Jan 30, 2024
Check valve 1
8.9 psid
Check valve 1 closed tight
Yes
Check valve 2
3.6 psid
Relief valve opened at
3.8 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Alex Benton, current on the service date
  • All required fields present
  • Address matches parcel 001-17-01104
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

6323 Orchard Ct
Owner: Calloway Holdings LLC
Parcel 001-17-01104