Back to the backflow review queue

Backflow assembly test: Station Diner

Approved

Filed Mar 29, 2025 by Sam Brandt, Ridge Backflow Testing. Filed from a phone.

Report

Date of service
Mar 29, 2025
Assembly type
RP
Serial number
A563767
Size
1
Test gauge serial
G-3306
Gauge calibration date
Jul 17, 2024
Check valve 1
4 psid
Check valve 1 closed tight
Yes
Check valve 2
2.6 psid
Relief valve opened at
2.3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Sam Brandt, current on the service date
  • All required fields present
  • Address matches parcel 001-82-01288
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

9217 Cedar Hollow Way
Owner: Marsh Holdings LLC
Parcel 001-82-01288