Backflow assembly test: 2013 Stone Gate Way

Approved

Filed Jul 29, 2026 by Riley Danner, Ridge Backflow Testing. Read in from a paper form and confirmed by staff.

Report

Date of service
Jul 29, 2026
Assembly type
RP
Serial number
A688506
Size
1
Test gauge serial
G-2247
Gauge calibration date
Jun 24, 2026
Check valve 1
8.8 psid
Check valve 1 closed tight
Yes
Check valve 2
2.4 psid
Relief valve opened at
2.7 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Riley Danner, current on the service date
  • All required fields present
  • Address matches parcel 001-29-01349
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

2013 Stone Gate Way
Owner: Alex Wexler
Parcel 001-29-01349