Back to the backflow review queue

Backflow assembly test: Blue Heron Elementary School

Approved

Filed Jun 23, 2024 by Sam Brandt, Ridge Backflow Testing. Filed from a phone.

Report

Date of service
Jun 23, 2024
Assembly type
DC
Serial number
A306785
Size
2
Test gauge serial
G-2806
Gauge calibration date
May 10, 2024
Check valve 1
7 psid
Check valve 1 closed tight
Yes
Check valve 2
1.8 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Sam Brandt, current on the service date
  • All required fields present
  • Address matches parcel 001-71-01194
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

6166 Ridgeview Trl
Owner: Kessler Holdings LLC
Parcel 001-71-01194