Backflow assembly test: Crossroads Grill
ApprovedFiled Oct 18, 2025 by Rowan Okafor, Ridge Backflow Testing. Read in from a paper form and confirmed by staff.
Report
- Date of service
- Oct 18, 2025
- Assembly type
- DC
- Serial number
- B105681
- Size
- 4
- Test gauge serial
- G-9093
- Gauge calibration date
- Aug 25, 2025
- Check valve 1
- 8.6 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.8 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Rowan Okafor, current on the service date
- All required fields present
- Address matches parcel 001-22-01340
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.
Property
8556 Orchard Ln
Owner: Fairley Holdings LLC
Parcel 001-22-01340