Backflow assembly test: Crossroads Grill

Approved

Filed Jun 13, 2025 by Parker Kessler, Keystone Backflow Testing. Filed from a phone.

Report

Date of service
Jun 13, 2025
Assembly type
RP
Serial number
A862151
Size
4
Test gauge serial
G-1634
Gauge calibration date
Oct 10, 2024
Check valve 1
4.1 psid
Check valve 1 closed tight
Yes
Check valve 2
3.9 psid
Relief valve opened at
2.9 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Parker Kessler, current on the service date
  • All required fields present
  • Address matches parcel 001-46-01283
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.