Backflow assembly test: 8341 Pine Knoll Way

Approved

Filed Aug 19, 2026 by Sam Brandt, Ridge Backflow Testing. Read in from a paper form and confirmed by staff.

Report

Date of service
Aug 19, 2026
Assembly type
RP
Serial number
B697260
Size
1
Test gauge serial
G-4634
Gauge calibration date
Apr 24, 2026
Check valve 1
6.7 psid
Check valve 1 closed tight
Yes
Check valve 2
1.1 psid
Relief valve opened at
3.3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Sam Brandt, current on the service date
  • All required fields present
  • Address matches parcel 001-89-01167
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.