Backflow assembly test: 3910 Meadow Lark Ct

Approved

Filed Oct 2, 2025 by Rowan Okafor, Ridge Backflow Testing. Read in from a paper form and confirmed by staff.

Report

Date of service
Oct 2, 2025
Assembly type
RP
Serial number
B425547
Size
1
Test gauge serial
G-3180
Gauge calibration date
Jan 28, 2025
Check valve 1
8.3 psid
Check valve 1 closed tight
Yes
Check valve 2
1.8 psid
Relief valve opened at
3.2 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Rowan Okafor, current on the service date
  • All required fields present
  • Address matches parcel 001-18-01102
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

3910 Meadow Lark Ct
Owner: Hayden Okafor
Parcel 001-18-01102